We Wrote The Book on Grounding and Earthing

Toll Free: 888.367.0888

Ask The Experts Blog

What is the purpose of the PVC sleeve in concrete grounding?


Doug asks us:

What is the purpose of PVC sleeves in concrete? As far as I know, there is minimal chemical reaction between copper and concrete, and the sleeve is meant to protect the area where the ground wires exit the concrete, assuming you seal it up with silicone. Is there any reference material discussing ground wire installation methods in concrete? This is not technically for a Ufer ground, but it is meant to keep all metallic objects at the same potential, including rebar. Thanks!

250-23_FINAL_300dpiHi Douglas,

The PVC sleeve is a requirement under NEC 250.64(B) for mechanical stress relief of equipment grounding conductors. There is an excellent illustration in the NEC Handbook at 250.52(A)(3) Exhibit 250.23.

I do not recommend PVC sleeves as there are a number of vendors who sell 2 and 4 hole brass bonding plates specifically designed to provide a rebar/concrete interface connection point. A grounding electrode conductor that is broken entering a concrete slab, whether protected by a PVC sleeve or not, will require you to bust the concrete slab up to repair it. A brass plate with bolt holes in it makes for a quick and simple repair. It also allows for future testing as a simple wrench can remove the connections.

Corrosion is not the reason for the PVC sleeve, however it would be advisable to test the concrete prior to pouring to ensure that the pH is slightly on the caustic side. Acids corrode copper, caustics protect.

Also, please note that concrete has a very high level of water content, even when cured as relative humidity levels between 60 to 95% RH are common. Because concrete is so porous and tends to absorb water, vapor barriers are commonly installed between the slab and the earth, so as to prevent water seepage in to a building. In fact, your moisture content in your slab will vary with the seasons. Humidity monitors are sometimes installed directly into concrete slabs for monitoring reasons. This is why concrete will explode if you put a blow torch to it or pass a large electrical current through it, the inherent water in the concrete will turn in to steam, thereby exploding the concrete.

Best regards,

The Engineering Team at E&S Grounding Solutions

 

Photo credit: E&S Grounding Solutions

 

Leave a Reply